{"product_id":"pepperl-fuchs-kfd2-crg2-ex1-d-transmitter-power-supply","title":"Pepperl+Fuchs KFD2-CRG2-Ex1.D – Transmitter Power Supply with Trip Values","description":"\u003ch2\u003eProduct Overview\u003c\/h2\u003e\n\u003cp\u003eThe Pepperl+Fuchs KFD2-CRG2-Ex1.D is a 1-channel isolated barrier transmitter power supply with trip values. It powers 2-wire and 3-wire transmitters, or accepts 2-wire current sources, in the hazardous area and provides a 0\/4 … 20 mA analogue output together with two relay contact outputs for high\/low alarms.\u003c\/p\u003e\n\u003cp\u003eAlarm set points, energised\/de-energised delays (0 … 250 s) and a linearisation function of up to 20 points are programmed via the front keypad and display or with PACTware. Line fault detection monitors the input circuit, and the module is suitable for applications up to SIL 2 to IEC\/EN 61508 \/ IEC\/EN 61511.\u003c\/p\u003e\n\u003ch2\u003eKey Features\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eManufacturer:\u003c\/strong\u003e Pepperl+Fuchs\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel:\u003c\/strong\u003e KFD2-CRG2-Ex1.D\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProduct type:\u003c\/strong\u003e Transmitter Power Supply with Trip Values\u003c\/li\u003e\n\u003cli\u003e1-channel isolated barrier\u003c\/li\u003e\n\u003cli\u003eInput for 2-wire and 3-wire transmitters and 2-wire current sources\u003c\/li\u003e\n\u003cli\u003e0\/4 … 20 mA analogue output\u003c\/li\u003e\n\u003cli\u003e2 relay contact outputs with programmable high\/low alarms\u003c\/li\u003e\n\u003cli\u003eAdjustable energised\/de-energised delay\u003c\/li\u003e\n\u003cli\u003eLinearisation function (max. 20 points)\u003c\/li\u003e\n\u003cli\u003eLine fault detection; up to SIL 2\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable style=\"width:100%;border-collapse:collapse;margin:0 0 1rem\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eManufacturer\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003ePepperl+Fuchs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003ePart number\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eKFD2-CRG2-Ex1.D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eProduct type\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e1-channel transmitter power supply with trip values \/ isolated barrier\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eSignal type\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eAnalogue input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eRated supply voltage\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e20 … 30 V DC (Power Rail or terminals 23+, 24-)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003ePower consumption\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e2.5 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eInput signal\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e0\/4 … 20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eAvailable voltage\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e≥ 15 V at 20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eLine fault detection\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eBreakage I \u0026lt; 0.2 mA; short circuit I \u0026gt; 22 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eOutputs I, II\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eRelay; 253 V AC \/ 2 A \/ cos φ ≥ 0.7; 40 V DC \/ 2 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eOutput III\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e0 … 20 mA or 4 … 20 mA, load max. 650 Ω; NE43 fault signal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eDelay\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e0 … 250 s, adjustable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eConfiguration\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eFront keypad and display, or PACTware\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eFunctional safety\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eSIL 2 (IEC\/EN 61508 \/ IEC\/EN 61511)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eAmbient temperature\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e-20 … 60 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eDegree of protection\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eDimensions\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e40 x 119 x 115 mm (W x H x D), housing type C2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eMass\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e300 g\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eMounting\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003e35 mm DIN mounting rail (EN 60715)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eATEX\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eTÜV 01 ATEX 1701 — II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I; TÜV 02 ATEX 1885 X — II 3G Ex nA nC IIC T4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eIECEx\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eIECEx TUN 09.0007, IECEx TSA 18.0007X\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\" style=\"border:1px solid rgba(0,0,0,.12);text-align:left;width:38%;padding:.6rem .9rem;vertical-align:top\"\u003eOther approvals\u003c\/th\u003e\n\u003ctd style=\"border:1px solid rgba(0,0,0,.12);padding:.6rem .9rem;vertical-align:top\"\u003eUL (E223772)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\n\u003cp\u003e\u003cem\u003eSpecifications are taken from Pepperl+Fuchs manufacturer data. Always confirm critical values — particularly hazardous-area and functional-safety data — against the current datasheet, certificates and instruction manual before installation.\u003c\/em\u003e\u003c\/p\u003e\n\u003ch2\u003eApplications\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eLevel and pressure transmitters with local high\/low alarm relays\u003c\/li\u003e\n\u003cli\u003eAnalogue signal isolation with limit monitoring\u003c\/li\u003e\n\u003cli\u003ePump and process protection trips\u003c\/li\u003e\n\u003cli\u003eSIL 2 limit value monitoring\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003eInstallation and Compatibility\u003c\/h2\u003e\u003cp\u003eDIN rail mounting (40 mm wide) with 24 V DC from the Power Rail or terminals 23+\/24-. Transmitter connects to terminals 1, 2, 3; relays to 10–12 and 16–18; analogue output to 8+\/7-. Configure via the keypad or PACTware using the programming socket.\u003c\/p\u003e\n\u003ch2\u003eFrequently Asked Questions\u003c\/h2\u003e\n\u003ch3\u003eWhat is the Pepperl+Fuchs KFD2-CRG2-Ex1.D?\u003c\/h3\u003e\u003cp\u003eThe Pepperl+Fuchs KFD2-CRG2-Ex1.D is a 1-channel isolated barrier transmitter power supply with trip values. It powers 2-wire and 3-wire transmitters, or accepts 2-wire current sources, in the hazardous area and provides a 0\/4 … 20 mA analogue output together with two relay contact outputs for high\/low alarms.\u003c\/p\u003e\n\u003ch3\u003eWhat supply does the KFD2-CRG2-Ex1.D need?\u003c\/h3\u003e\u003cp\u003e20 … 30 V DC (Power Rail or terminals 23+, 24-).\u003c\/p\u003e\n\u003ch3\u003eHow do I get a price for the KFD2-CRG2-Ex1.D?\u003c\/h3\u003e\u003cp\u003eThis product is sold on a price on availability basis. Use the \u003ca href=\"#poa-enquiry\"\u003eenquiry form\u003c\/a\u003e on this page with your quantity and application details and the Valves UK team will reply with pricing and lead time.\u003c\/p\u003e\n\u003ch2\u003eTechnical Documentation\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/files.pepperl-fuchs.com\/webcat\/navi\/productInfo\/pds\/255620_eng.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePepperl+Fuchs KFD2-CRG2-Ex1.D datasheet (PDF)\u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/www.pepperl-fuchs.com\/en\/products-gp25581\/58378\" target=\"_blank\" rel=\"noopener\"\u003eKFD2-CRG2-Ex1.D on the Pepperl+Fuchs website\u003c\/a\u003e (certificates, manuals and drawings)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003eRelated Products\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003e\u003ca href=\"\/products\/pepperl-fuchs-kfd2-ufc-ex1-d-frequency-converter\"\u003ePepperl+Fuchs KFD2-UFC-Ex1.D – Universal Frequency Converter\u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"\/products\/pepperl-fuchs-kfd2-gut-ex1-d-temperature-converter\"\u003ePepperl+Fuchs KFD2-GUT-Ex1.D – Temperature Converter with Trip Values\u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"\/collections\/pepperl-fuchs\"\u003eView the full Pepperl+Fuchs range at Valves UK\u003c\/a\u003e\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003ePrice and Availability\u003c\/h2\u003e\u003cp\u003e\u003cstrong\u003ePrice on Availability (POA)\u003c\/strong\u003e\u003c\/p\u003e\u003cp\u003eContact Valves UK for pricing, product availability and technical enquiries regarding the Pepperl+Fuchs KFD2-CRG2-Ex1.D. Please include your required quantity and any relevant application details when submitting your enquiry.\u003c\/p\u003e","brand":"Pepperl+Fuchs","offers":[{"title":"Default Title","offer_id":60161085276485,"sku":"KFD2-CRG2-Ex1.D","price":0.0,"currency_code":"GBP","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0956\/5542\/8421\/files\/pepperl-fuchs-kfd2-crg2-ex1-d-transmitter-power-supply-with-trip-values.jpg?v=1794323911","url":"https:\/\/valvesuk.com\/products\/pepperl-fuchs-kfd2-crg2-ex1-d-transmitter-power-supply","provider":"Valves UK","version":"1.0","type":"link"}